Operating Your Text Display (TD) Device
5.5 Viewing the Screens and the Alarms
Text Display (TD) User Manual
116 System Manual, 08/2008, A5E00765548-03
Notice
Due to restrictions in the format used to store real (floating-point) numbers in both the S7-
200 CPU and the TD device, the accuracy of the number is limited to six significant digits.
Editing a real number with more than six digits may not change the value of the variable, or
may cause other digits within the number to change:
Changing the least significant (right-most) digit of a real-number variable with more than
six digits may have no effect. For example, if you try to change the "9" in "1234.56789",
the value of the variable does not change.
Changing the most significant (left-most) digit of a real-number variable with more than
six digits may cause other (less significant) digits in the variable to change.