Micro Automation Set 14 Entry ID 21062588
V2.0 05/18/05 21/35
Copyright © Siemens AG 2005 All rights reserved
Set14_DocTech_V2.0_en.doc
8.
Connect S7-200 “Backup” to S7-200
“Basis” via SCALANCE X108.
9. Restart S7-200 “Basis”.
10. The USB/PPI cable can now be removed.
Configuring S7-300 “Backup” station with MicroWin project
Table 5-5
No. Function Comment
1.
Connect the S7-300 CPU to a DC 24V
power supply.
2.
Plug the micro memory module in the
S7-300 CPU.
3. Switch on the power supply.
4.
Open the included S7-300 project
“Set14_S7-300_V2-0.zip” on the
configuration PC using STEP 7 and make
the following settings in STEP 7:
Set the access point in “Set PG/PC
Interface” to “S7ONLINE Æ
TCP/IP(Auto) network controller”
S
64 KB
CPU 315 PN/DP
S7-200 Basis”
IE cable
SCALANCE X108
S7-200 Backup”
IE cable