Micro Automation Set 14 Entry ID 21062588
V2.0 05/18/05 22/35
Copyright © Siemens AG 2005 All rights reserved
Set14_DocTech_V2.0_en.doc
5.
Ensure that the configuration PC is
connected to S7-300 “Backup” via
SCALANCE X108. Load the program to
the S7-300 CPU. When configuring the
S7-300 CPU for the first time, it is
required to select the connection partner
using the MAC address.
6.
Connect S7-300 “Backup” to S7-200
“Basis” via SCALANCE X108.
7. Restart S7-200 “Basis”.
Configuring S7-400 “Backup” station with STEP 7 project
Table 5-6
No. Function Comment
1.
Connect the S7-400 PS to an AC 230 V
supply voltage.
2. Switch on the power supply.
3.
Open the included S7-400 project
“Set14_S7-400_V2-0.zip” on the
configuration PC using STEP 7 and make
the following settings in STEP 7:
Set the access point in “Set PG/PC
Interface” to “STEP7 Æ TCP/IP(Auto)
network controller”
Configuration PC
IE cable
SCALANCE X108
CPU 315 PN/DP
IE cable
S7-300 Backup”
IE cable
SCALANCE X108
S7-200 Basis”
IE cable