STEP 7 special diagnostics
12.3 Starting diagnostics
Configuring and commissioning S7 CPs for Industrial Ethernet
Configuration Manual, 09/2013, C79000-G8976-C182-13
209
1. Set the interface of your PG/PG to TCP/IP.
2. In the STEP 7 project for the network attachment of your PG/PC, enter the use of a
default router.
3. As the address of the default router, enter the IP address of the interface of the Advanced
CP that is accessible in your own subnet (in the figure 157.55.80.1).
4. Start STEP 7 special diagnostics as described above.
The connection is established from the PG/PC to the destination node via the two
interfaces of the Advanced CP.
12.3.2
Use as PC station - setting the gateway for "PC internal"
If you use your device as a PC station (PC internal), you need to make settings in the dialog
section "Gateway". You will need to set parameters for the gateway even if do not need to
pass through any further gateway to reach the destination station.
Select the following settings:
Gateway attachment: MPI/PROFIBUS/AUTO
Node address (gateway)
Enter the index of the module here.
The index is the virtual slot address of the component (can be displayed using the Station
Configuration Editor). The index is identical to the slot number selected during
configuration of the PC station in STEP 7!
S7 subnet ID of target network
You will find an example here:
Figure 12-6 Example of settings with "PC internal"