Configuring the Ethernet CP with STEP 7
3.3 Setting further CP properties
Configuring and commissioning S7 CPs for Industrial Ethernet
Configuration Manual, 09/2013, C79000-G8976-C182-13
63
3.3.14
"PROFINET" parameter group
"PROFINET" Tab
Here, you specify the properties of the Ethernet CP for PROFINET IO and PROFINET CBA.
Table 3- 4 Options / input area of the "PROFINET" parameter group
Option / input area
Meaning / effect
Operating mode *
)
Depending on the CP device type, you can select the possible
modes here in which the S7 station can be operated on
PROFINET.
PROFINET IO controller
With this option, you specify whether or not the Ethernet CP
will be operated as a PROFINET IO controller. You can also
specify this by assigning a PROFINET IO system to the CP in
HW Config using the shortcut menu of the right mouse button.
PROFINET IO device
With this option, you specify whether or not the Ethernet CP
will be operated as a PROFINET IO device. In a further step,
you assign the CP to the PROFINET IO system as a
PROFINET IO device.
Device name
Name of the device (acc. to DNS conventions). The device name
must be unique on the Ethernet subnet. When the CP is operating
as a PROFINET IO controller, the device name is derived from the
short name.
STEP 7 allows you to add the name of the IO system to the device
name automatically. If you require this, select the "Use name in
device/controller" option in the properties of the PROFINET IO
system.
CBA communication
To be able to use the S7 station with PROFINET CBA, specify the
CP to be used for the componentization for PROFINET CBA or
SIMATIC iMap.
*
)
For CPs with configurable ports, set the "PROFINET IO controller" mode in the parameter
assignment of the interface slot.
3.3.15
"Security" parameter group (STEP 7 V5.5)
In this parameter group, you can activate the security functions for certain Ethernet CPs.
Requirement for activating Security:
The Security Configuration Tool (SCT) configuration tool is installed.
The gigabit interface is networked.