Configuring communications connections
5.4 Configuring ISO transport connection properties
Configuring and commissioning S7 CPs for Industrial Ethernet
Configuration Manual, 09/2013, C79000-G8976-C182-13
99
5.4
Configuring ISO transport connection properties
5.4.1
Specifying ISO transport addresses
Address parameters
An ISO connection is specified by the local and remote connection endpoint.
Local addresses:
Local MAC address and local TSAP
(Transport Service Access Point)
Remote addresses:
Remote MAC address and remote TSAP
Note
The TSAPs of an ISO transport connection must match up as follows:
Remote
TSAP (on Ethernet CP) = local TSAP (in destination station);
Local TSAP (on Ethernet CP) = remote TSAP (in destination station);
Configuring addresses
STEP 7 displays proposed values for the relevant local and remote address information. If
necessary, you can set the TSAPs individually.
TSAP format
ISO transport connections have a TSAP length of 1 to 16 bytes. When you are entering
values, the current length is displayed automatically (visible display: 16 ASCII characters).
Local and remote TSAPs can be entered as hexadecimal values or as an ASCII string.
If you enter the TSAP as an ASCII string, the characters are also displayed in
hexadecimal format.