10.8 Retrigger reference point
FM 352 electronic cam controller
Operating Instructions, 05/2011, A5E01071724-03
121
Data used in the channel DB
Address Name Type Start value Comment
34.3 REFTR_ON BOOL FALSE 1 = retrigger reference point
25.0 SYNC BOOL FALSE 1 = axis is synchronized
Data used in the parameter DB
Address Name Type Start value Comment
44.0 REFPT DINT L#0 Reference point coordinate
52.0 RETR_TYPE DINT L#0 Type of reference point retriggering
Effects of the setting
FM 352 evaluates the zero mark signal and reference point switch based on the direction
of movement of the axis.
It evaluates the positive edges when the axis moves in positive direction.
It evaluates the negative edges when the axis moves in negative direction.
It sets the actual position to the value of the reference point coordinate.
The working range is physically shifted on the axis.
The various points retain their original values, but are now at new physical positions.
Cam status changes that would normally trigger a hardware interrupt can be lost.
The SYNC bit is set in the checkback signals.
Note
For information on switching characteristics of time-based cams, refer to chapter
"Influence of settings on the switching characteristics of time-based cam
s (Page 103)".