Programming without SFB 52 and SFB 53
D.10 Technical specifications
FM 352 electronic cam controller
214 Operating Instructions, 05/2011, A5E01071724-03
D.10 Technical specifications
Overview
The table below provides an overview of the technical data of the FM 352 functions.
Table D- 2 Technical data of FM 352 functions
No. Block name Version Allocation
in load
memory
(bytes)
Allocation in
work
memory
(bytes)
Allocation in
local data
area
(bytes)
MC7 code /
data
(bytes)
System functions
called
FC 0 FC CAM_INIT 1.0 192 138 2 102
FC 1 FC CAM_CTRL 1.0 5232 4754 32 4718 SFC 58: WR_REC,
SFC 59: RD_REC
FC 2 FC CAM_DIAG 1.0 1758 1614 42 1578 SFC 59: RD_REC
Channel DB - 986 804 - 372
Parameter DB 16
Parameter DB 32
Parameter DB 64
Parameter DB 128
-
-
-
-
616
808
1192
1960
336
528
912
1680
-
-
-
-
300
492
876
1644
Diagnostic DB - 460 338 - 302
Module cycle
The module updates the checkback data (except in the pulses measuring system) every
4 ms.
In the pulses measuring system, the data for the actual position value and track signals are