Product Information on the Manual S7-300 Module Specifications, Edition 11/2002
A5E00213444-02
Suppression of interference, Limits of Error
Crosstalk between
outputs
> 100 dB
Operational limit (in the entire temperature range, with
reference to the output range)
S Voltage outputs ±0.12%
S Current outputs ±0.18%
Basic error (operational limit at 25° C, referred to output
range)
S Voltage outputs
±10 V
0 to 10 V
1 to 5 V
±0.02%
±0.02%
±0.04%
S Current outputs
±20 m
0 to 20 mA
4 to 20 mA
±0.02%
±0.02%
±0.04%
Temperature error (with
reference to the output range)
S Voltage outputs
S Current outputs
± 0.0025% / K
± 0.004% / K
Linearity error (with reference to
the output range)
±0.004%
Repeat accuracy (in the steady
state at 25° C, referred to the
output range)
±0.002 %
Output ripple; band width 0 to
50 kHz (with reference to the
output range)
±0.05 %
Status, Interrupts, Diagnostics
Interrupts
S Diagnostic Interrupt Programmable
Diagnostic functions Programmable
S Group error display Red LED (SF)
S Diagnostic information
readable
Possible
Substitute value can be applied Yes, programmable
Data for Selecting an Actuator
Output ranges (rated values)
S Voltage ±10 V
0 to 10 V
1 to 5 V
S Current ±20 mA
0 to 20 mA
4 to 20 mA
Load resistance (in the nominal
range of the output)
S For voltage outputs
Capacitive load
min. 1 k
max. 1 µF
S For current outputs
Inductive load
max. 500
max. 1 mH
Voltage outputs
S Short-circuit protection
S Short-circuit current
Yes
max. 40 mA
Current outputs
S No-load voltage max. 18 V
Destruction limit against
voltages/currents applied from
outside
S Voltage at outputs to M
ANA
max. 15 V continuous
75 VDC for max. 0.1 s
(pulse duty factor 1 :
20)
S Current max. 50 mA DC
Connection of actuators
S For voltage output
Four-conductor
connection (measuring
circuit)
Possible
S For current output
Two-conductor
connection
Possible

Other manuals for Siemens S7-300