Analog modules
9.3 SM 336; F-AI 6 x 0/4 ... 20 mA HART
Fail-safe signal modules
250 Installation and Operating Manual, 01/2010, A5E00085586-10
For information about the Zener diodes, refer to chapter "Calculation of the residual supply
voltage at the transducer (Page 239)".
WARNING
To achieve SIL3/Cat.4/PLe using this wiring, you must use a suitably qualified sensor.
Note
You can supply the two F-SMs from two power supply units. If you use two power supply
units, the two grounds on the F-SMs will have to be connected with each other.
Assignable parameters for application 6
Table 9- 20 Parameters for application 6 of SM 336; F-AI 6 x 0/4 ... 20 mA HART
Parameters Range of values in safety mode Type Effective range
Diagnostic interrupt Activated/deactivated Static Module
Behavior after channel fault Passivate the entire
module/Passivate the channel
Static Module
HART_Gate Off/On/Can be switched Static Module
Interference frequency
suppression
50 Hz/60 Hz Static Module
Evaluation of the sensors 1oo2 evaluation* Static Channel
Measuring range 4 to 20 mA, 0 to 20 mA Static Channel
F-wire break detection activated/deactivated
(in the 4 to 20 mA measuring range)
Static Channel
Smoothing 1 / 4 / 16 / 64 conversion cycles Static Channel
Discrepancy time (ms) 0 to 30000 Static Channel
Tolerance window (%)
absolute
0.2 to 20 Static Channel
Tolerance window (%)
relative
0.2 to 20 Static Channel
Standard value MAX/MIN Static Channel
HART function Activated/deactivated Static Channel
HART repetitions 0 to 255 Static Channel
HART group diagnostics Activated/deactivated Static Channel
Redundancy Activated/deactivated Static Channel
* If you are evaluating sensors in your safety program (e.g., in
S7 F Systems
using F-block
F_1oo2AI), configure "1oo1 evaluation".