Analog modules
9.3 SM 336; F-AI 6 x 0/4 ... 20 mA HART
Fail-safe signal modules
Installation and Operating Manual, 01/2010, A5E00085586-10
251
Discrepancy analysis for fail-safe analog input modules
If you have configured 1oo2 evaluation, you can configure a discrepancy time and an
absolute and a relative tolerance window for each channel pair of the module. In addition,
configure the standard value (MIN = lower value / MAX = higher value) to be applied and
transferred to the F-CPU.
If the difference between the two redundant input channels of the channel pair exists longer
than the configured discrepancy time, an error is signaled and the fail-safe value (7FFF
H
) is
transferred. In
S7 Distributed Safety
, the fail-safe value 0 is provided in the PII for the safety
program in place of 7FFF
H
. In
S7 F/FH Systems
the fail-safe value assigned at the input
SUBS_V of the channel driver will be provided in the PII.