Manual for installation of the Sensformer® Connectivity Device
© 2020 Siemens Energy Page 25
current is 20A RMS. In this case the user should configure gain to
1000 and offset to 0.
5.2.3. PT100 input
The Sensformer Connectivity Device has a dedicated input
channel for 4 wire PT100 connection.
The parameters of the PT100 input channel are the following:
Number of
PT100 inputs
1
Terminal type
4-wire
Separation Class
Class III (SELV)
Terminal isolation
3 kV
Measurement range
0 – 200 Ohms
Measuring current
1 mA
Size of conductor
1.5 mm
2
Table 13 - Parameters of PT100 input
Figure 30 - Schematic of PT100 input
5.2.4. Digital inputs
The digital inputs are used to detect the present of voltage, thus
the operation of contact type sensors.
The parameters of the digital input channels are the following:
Number of
digital inputs
2
Logic 1 levels
48 240 VAC (adjustable) 50/60 Hz
or 48-240 VDC (adjustable)
Terminal type
2 poles
Terminal isolation
AC 3 kV
Polarity
Independent
Input impedance
88 kOhm
Size of conductor
1.5 mm
2
Table 14 - Parameters of digital inputs
Figure 31 - Schematic of Digital Input
5.2.5. Power supply
The power supply is responsible for providing the necessary DC
power for the different functional parts of the device along with
the analog input channels, and the PT100 channel. The power
supply is protected against incoming network disturbances. The
power supply is protected against overvoltage and overcurrent,
protecting the inner parts of the device.
Input voltage
100 240 VAC (50Hz/60Hz)
Power consumption
< 15 VA AC
Terminal type
3 poles (L, N and PE)
Terminal isolation
AC 3 kV
Polarity
AC:
L: line, N: Neutral, PE: Protective
Earth
Size of conductor
1.5 mm
2
Table 15 - Parameters of power supply