Manual for installation of the Sensformer® Connectivity Device
© 2020 Siemens Energy Page 34
ModBus – RTU:
Figure 49- ModBus - RTU on Settings page
Poll interval in seconds: poll interval time to the ModBus
sensors on RS485.
SSH logger:
Figure 50- SSH logger on Settings page
Enabled: 0 disable, 1 enable,
Check certificate: 0 – no check it, 1 – check it,
IP address: send the log to this address. It can be local or
remote too.
Port: send the log to this TCP port.
Download log button: save the device log as a txt file.
NOTE
For security reasons, always set up a user name and password
on first login!
Creating a secure password is an important part of protecting
your device. A strong password is at least 8 characters or more
and can be a combination of letters, numbers, and symbols.
6.2.2.7. Admin
The admin page is available only with admin role. The editors
cannot see the admin page.
Figure 51 - Admin page
User management:
Figure 52- User management on the Admin page
: add new user
: edit the user’s password and / or role,
: delete user
Password policy:
Figure 53- Password policy on the Admin page
digit: minimum number of digit characters in the passwords,
lower case: minimum number of lower letter characters in
the passwords,
upper case: minimum number of upper letter characters in
the passwords,