Applications
3.1 Use of the 3VA UL molded case circuit breakers in line protection
3VA molded case circuit breakers with UL and IEC certification
126 Manual, 01/2019, L1V30435333-01
ETU556 / ETU856 parameters, 3-pole:
1)
only 3-pole version with external current transformer for N conductor
ETU556 / ETU856 parameters, 4-pole:
•
I
r
Adjustable from 0.4 to 1.0 x I
n
in absolute current values
I
r
= 40 A: In steps of 0.5 A
I
r
≥ 100 A: In steps of 1 A
•
t
ld
Adjustable from 0.5 to 13 / 15 / 17 / 20 / 25 s (dependent on rated operational
current and frame size)
with a reference point of 6 x I
r
.
In steps of 0.1 s
The ETU556 LSI(G) and ETU856 LSI(G) have a permanently active thermal memory.