Accessories
4.7 Locking and interlocking
3VA molded case circuit breakers with UL and IEC certification
Manual, 01/2019, L1V30435333-01
313
Installing the cylinder lock in the accessory compartment
The cylinder lock (type Ronis) is installed with the adapter kit and the "Interlocking" cylinder
lock housing in the right-hand accessory compartment of the molded case circuit breaker.
Adapter kit
Cylinder lock housing for interlocking
Actuating lever
Cylinder lock (type Ronis)
Accessory cover
1. Remove the accessory cover
from the 3VA UL molded case circuit breaker.
2. From the rear of the lid of the accessory cover, drill a hole through the lid at the position
designated for the cylinder lock housing and remove burrs with a file.
In addition, introduce as precise a gap as possible for anti-rotation protection of the
cylinder lock housing.
3. Insert a cylinder lock (type Ronis)
and the locking version of the cylinder lock housing
in the drilled hole and connect it securely to the accessory cover via the actuating
lever.
4. Install the adapter kit
in the right-hand accessory compartment of the 3VA UL molded
case circuit breaker.
5. Reattach the accessory cover to the 3VA UL molded case circuit breaker.
A cylinder lock (type Ronis) is installed for each 3VA UL molded case circuit breaker to be
interlocked.