Technical data
12.14 Shunt release
3VL molded-case circuit breakers
182 System Manual, 03/2009, 110 0110 - 02 DS 01
12.14 Shunt release
The shunt releases of the SENTRON VL circuit breakers have the following technical data:
Table 12- 46 Shunt releases for VL160X, VL160 to VL400
Group 1
VL160X VL160 VL250 VL400
Response voltage: Pick-up (circuit breaker
trips) [V]
0.7-1.10 V
s
0.7-1.10 V
s
0.7-1.10 V
s
0.7-1.10 V
s
Power consumption
AC 50 / 60 Hz [VA] 48-60 V
110-127 V
208-277 V
380-600 V
158-200
136-158
274-350
158-237
158-200
136-158
274-350
158-237
158-200
136-158
274-350
158-237
158-200
136-158
274-350
158-237
DC [W] 12 V
24 V
48-60 V
110-127 V
220-250 V
110
110
110-172
220-254
97-110
110
110
110-172
220-254
97-110
110
110
110-172
220-254
97-110
110
110
110-172
220-254
97-110
Max. in-service period [s] Interrupts automatically
Max. opening (release) time [ms] 50 50 50 50
Fuse (time-lag) [A]
Circuit breaker, [A]
C characteristic
4
(AC 48-60, 110-127 V,208-277 V)
2
(all others)
5