Technical data
12.16 Auxiliary switches and alarm switches
3VL molded-case circuit breakers
186 System Manual, 03/2009, 110 0110 - 02 DS 01
Technical data
Contact reliability
Test voltage/test current
5 V/1 mA
Short-circuit protection weld-free in accordance with IEC 60947-5-1
• DIAZED fuse links, utilization category gL/gG
• Miniature circuit breaker with C characteristic in accordance with
IEC 60898 (VDE 0641)
10 A TDz, 16 A D
10 A
Connection cross-sections
• Screw-type terminals
– Stranded, with end sleeves in accordance with DIN 46228
– Solid
– Solid, with end sleeves in accordance with DIN 46228
– Single- or multi-core
2 × (0.5 to 1.5) mm²
2 × (1 to 2.5) mm²
2 × (0.5 to 0.75) mm²
2 × AWG 18 to 14
Tightening torques
• Connection screws
0.8 Nm
Rated voltage
• Switching devices
300 V AC
Continuous current 10 A
Switching capacity A 300, R 300,
A 600 same polarity