System overview
4.2 Key data
3VL molded-case circuit breakers
36 System Manual, 03/2009, 110 0110 - 02 DS 01
4.2.3 General data - Trip units
Group No. 1
VL160X to VL400
Group No. 2
VL630 to VL1600
Undervoltage release
Response voltage:
• Drop (switch tripped) [V]
0.35 to 0.70 x U
s
0.35 to 0.70 x U
s
• Pick-up (switch can be
switched on) [V]
0.85 to 1.1 x U
s
0.85 to 1.1 x U
s
Power consumption (continuous operation) at:
• 50 / 60 Hz 24 V AC [VA]
1.4 1.2
• 50 / 60 Hz 110 to 127 V AC
[VA]
1.5 1.1
• 50 / 60 Hz 220 to 250 V AC
[VA]
1.5 2.1
• 50 / 60 Hz 208 V AC [VA]
1.8 2.2
• 50 / 60 Hz 277 V AC [VA]
2.1 1.6
• 50 / 60 Hz 380 to 415 V AC
[VA]
1.6 2.0
• 50 / 60 Hz 440 to 480 V AC
[VA]
1.8 2.3
• 50 / 60 Hz 500 to 525 V AC
[VA]
2.5 2.9
• 50 / 60 Hz 600 V AC [VA]
2.4 --
• 12 V DC (W)
0.75 1.2
• 24 V DC (W)
0.8 1.4
• 48 V DC (W)
0.8 1.5
• 60 V DC (W)
0.8 1.6
• 110 to 127 V DC (W)
0.8 1.2
• 220 to 250 V DC (W)
0.8 1.5
Max. opening (release) time
[ms]:
50 80