EasyManua.ls Logo

Siemens SENTRON 3VL160X - Page 122

Siemens SENTRON 3VL160X
318 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter assignment / addressing
9.1 Setting the parameters
3VL IEC molded case circuit breakers
122 System Manual, 11/2013, 110 0110 - 02 DS 03
I
2
t waveform:
A I
2
t waveform of the characteristic curve can be switched in (depending on the ETU), the
delay time t
sd
is based on the reference point 8 x I
R
. Two different procedures are used to
form the characteristic curve. As well as a fixed time delay for all currents in the
characteristic curve section, the I
2
t characteristic can also be used. The tripping time falls
continuously as the current increases, and the product of squared current and time remains
constant.
Figure 9-1 I
2
t
I instantaneous short-circuit protection I
i
:
On some trip units, the instantaneous short-circuit release I
i
can also be set. This refers to
the rated current I
n
of the molded case circuit breaker. It must always be noted that either the
instantaneous short-circuit release (I
i
) or the delayed short-circuit release (I
sd
) handles
personnel protection. The tripping current of the short-circuit release of the molded case
circuit breaker is set to a value that is at least 20% (tolerance of the trip unit) lower than the
lowest short-circuit current at the installation location and simultaneously higher than the
maximum operating current +20%. This guarantees that the circuit breaker will trip within the
required time even with the smallest short-circuit current, and that correct currents will not
result in unwanted trips.
G ground-fault protection I
g
:
The tripping value of the of the ground-fault release I
g
is fixed to the rated breaker current on
the ETU12 and ETU22. The tripping current of the ground-fault release can be set to
between 0.6 and 1 x I
n
, and the delay time t
g
can be set between 0.3 s and 0.6 s. The
measuring methods for the ground-fault protection are specified on the representation of the
trip unit. On the ETU42, the tripping current of the ground-fault release can be set to
between 0.4 and 1 x I
n
, and the delay time can be set between 0.1 s and 0.5 s.
Note
Ground-fault protection
It must be noted that the ground
-fault protection is not a residual-current operated circuit
break
er (FI or RCD in the building installation). Fault currents to ground therefore cannot be
detected, only ground "short"
-circuits.

Table of Contents

Related product manuals