Technical data
11.3 Configuration of main connections
3VL IEC molded case circuit breakers
136 System Manual, 11/2013, 110 0110 - 02 DS 03
Configuration of main connections
Main connections
Molded case circuit
breakers
Connection overview and further options
Box terminals Terminals with
screw connection
with metric thread
Circular conductor
terminal / multiple
feed-in terminal
Rear terminals Front-accessible
connecting bars
2)3)
1)
2)
2)
2)
□ Optional scope of supply
Not available
Connecting terminal plate for flexible busbar; not for 690 V AC / 600 V DC.
Multiple feed-in terminal
3)
Circular conductor terminal also available.
2)
• Solid or stranded cable;
copper only [mm²]
2.5 to 95 2.5 to 95 25 to
185
50 to
300
- - - -
• Finely stranded with end
sleeve [mm²]
2.5 to 50 2.5 to 50 25 to
120
50 to
240
- - - -
• Flexible busbar [mm]
12 x 10 12 x 10 17 x 10 25 x 10 - - - -
• Connecting terminal plate for
flexible busbar
1)
[mm]
- - - - 2 units
10 × 32
- - -
Circular conductor terminal
• Solid or stranded cable; Cu or
Al [mm²]
16 to 70 16 to 70 25 to
185
50 to
300
- - - -