Technical data
11.14 Position signaling switch
3VL IEC molded case circuit breakers
164 System Manual, 11/2013, 110 0110 - 02 DS 03
weld-free in accordance with IEC 60947-5-1
• NEOZED fuse links, utilization category gL / gG
• Miniature circuit breaker with C characteristic in accordance with
IEC 60898 (VDE 0641)
10 A TDz, 16 A D
10 A
• Stranded, with end sleeves in accordance with DIN 46228
• Solid or stranded (metric)
• Solid or stranded (AWG)
2 × (0.5 ... 1.5) mm²
2 × (1 ... 2.5) mm²
2 × AWG 18 ... 14
• Connection screws
0.8 Nm
• Switching devices
300 V AC
Position signaling switch
Position signaling switch
When a molded case circuit breaker is mounted in a withdrawable or plug-in assembly, the
position signaling switch, which is equipped with a changeover contact, is used to indicate
whether the molded case circuit breaker is in the connected or withdrawn position. Two
position signaling switches can be mounted in each withdrawable or plug-in base.
Figure 11-1 Position signaling switch