Parameterization and remote control
4.1 Parameterization of the protection parameters
3WA Air Circuit Breaker Communication
System Manual, 11/2021, 92310000004-02
31
Example: Protection parameter ST, setting Isd
Parameter for Isd Settable via Parameter
Register Read / write
sd
Source: Rotary switch position or e.SET
sd
ETU600 display / com-
munication
Setting Isd ETU600 display / com-
B 0x1F55 Read / write
ST
ETU600 display / com-
munication
ST
ETU600 display / com-
munication
Example of setting:
• I
r = 1000 A
• I
r e.SET = 8888 A (register 0x1F4E)
1. The rotary switch is at the position "2.5"
Setting for I
sd (register 0x1F46) is 2.5 x Ir 1000 A = 2500 A.
2. The rotary switch is at the position "e.SET"
Setting for I
sd (register 0x1F46) is 8888 A.