Parameterization and remote control
4.2 Close/open circuit breaker via Modbus TCP
3WA Air Circuit Breaker Communication
System Manual, 11/2021, 92310000004-02
33
4.2 Close/open circuit breaker via Modbus TCP
Closing or opening of the circuit breaker via the communication connection takes place by
means of commands. For information about the commands, see Chapter Writing commands
(Page 37).
Closing or opening of the circuit breaker via the communication connection requires
communication
-capable closing and opening coils (shunt trips). The closing coil (CC-COM)
ip (ST-
COM) can be ordered immediately with the ready4COM circuit breaker
or can be retrofit later.
Remote switching protection (RSP) must be deactivated on the COM190 communication
module in order to permit switching via the communication connection. For
more
information, refer to the 3WA Equipment Manual.
The value 0x815 is transferred in order to write the Close/Open command.
Whether or not the switching operation was successful can be queried in register 0xCB3B, see
also section Status of the mechanical system (Page 20).