PROFINET IO
6.3 Metering values, addressing und data traffic
3WA Air Circuit Breaker Communication
58 System Manual, 11/2021, 92310000004-02
Basic type 3
Basic type 3 was implemented according to the LVSG profile of the PROFINET user
organization (PNO) and comprises fourteen data blocks containing metering values. These
are preassigned such that unmodified use is only meaningful with a 3WA circuit breaker with
metering function.
The predefined data blocks cannot be modified.
Max. current in phase under highest load (u16)
Current in neutral conductor (u16)
Phase-to-phase voltage L12 (u16)
Phase-to-phase voltage L23 (u16)
Phase-to-phase voltage L31 (u16)
Line-to-neutral voltage L1N (u16)
Line-to-neutral voltage L2N (u16)
Line-to-neutral voltage L3N (u16)
Active energy import (u16)
Total 3-phase apparent power (u16)
Basic type 4
Basic type 4 comprises four data blocks. These are preassigned such that they are primarily
suitable for use with a 3WA circuit breaker without metering function. The most important
currents of the phases are transferred.
The predefined data blocks cannot be modified.
Current in phase 1 (float)
Current in phase 2 (float)
Current in phase 3 (float)
Max. current in phase under highest load (float)