Description
2.5 Electronic trip unit ETU600
3WA1 air circuit breaker
Equipment Manual, 02/2023, 92310000002-06
115
ETU600 LSI, ETU600 LSIG, ETU600 LSIG Hi-Z
Protective function Setting range for parameter sets A
Settings with rotary coding switch
only possible in parameter set A
L: Overload protection LT
r
n
0.5 / 0.6 / 0.7 / 0.75 / 0.8 / 0.85 / 0.9
/ 0.95 / 1.0 x I
n
r
r
At I
2
t: 0.5 ... 30 s
At I
4
1 / 2 / 5 / 8 / 10 / 14 / 17 / 21 / 25 s
r PAL
r
r PAL
r
L: Overload protection LT, neutral conductor
rN
n
4-pole: 0.2 x I
n
… I
n max
S: Delayed short circuit protection ST
sd
n
cw
max. 0.8 I
1)
1.5 / 2 / 2.5 / 3 / 4 / 5 / 6 / 8 / 10 x I
r
max. 0.8 x I
1)
sd
0.08 / 0.15 / 0.22 / 0.3 / 0.4 s
At I
2
t = ON:
0.1 / 0.2 / 0.3 / 0.4 s
ST ref
r
S: Directed short-time-delayed short-circuit protection dST (optional)
0.6 x I
n
… max. 0.8 x I
cw
1)
0.6 x I
n
… max. 0.8 x I
cw
1)
I: Instantaneous short-circuit protection INST
i
n
cs
max. 0.8 I
cs
1)
1.5 / 2 / 3 / 4 / 6 / 8 / 10 / 12 / 15 x
I
n
1)