Description
2.8 Communication and system connection
3WA1 air circuit breaker
Equipment Manual, 02/2023, 92310000002-06
153
Description of the status displays (normal operating states)
LED display is in combination mode (see section Special
operating states)
CubicleBUS
2
communication disturbed
Address conflict on the CubicleBUS
2
:
Two COM modules have been configured for the same role or
there is only one COM B and no COM A.
No CubicleBUS
2
nodes active
Modbus telegram received with correct checksum and
address of the device
No communication with Modbus client
Description of the status displays (special operating states)
Indication
Description
flashing green
alternately.
RTU is off.
Visual identification of the COM150 communications module
is active.
Visual identification can be activated in the SENTRON
powerconfig configuration software (blink mode).
The identification ends automatically after 10 seconds. You
can terminate identification before this time by pressing the
function button.
flashing red
alternately.
The COM150 communications module is not operational and
may need to be replaced.
CUB and RTU are off.
The COM150 communications module is starting up.
orange.
The device is restarting after a reset or after the auxiliary
voltage has been switched on.
The display is on for 1 second.