Description
2.8 Communication and system connection
3WA1 air circuit breaker
Equipment Manual, 02/2023, 92310000002-06
161
Commissioning via the USB-C interface of the circuit breaker
To commission a communication module via the USB-C interface of the 3WA circuit
breaker, proceed as follows:
1. Connect your notebook/PC to the USB-C interface of the 3WA circuit breaker.
2. Start the SENTRON powerconfig configuration software.
3. In the SENTRON powerconfig configuration software, drag a 3WA circuit breaker into
the project.
4. Select the USB interface as gateway.
5. Load the current parameters of the 3WA circuit breaker into the project.
6. Edit the network parameters of the communication module.
7. Load the changed parameters into the 3WA circuit breaker.
The communication module can then be accessed under the set network parameters.
8. Load the communication module into the powerconfig project to make further settings,
if necessary.
Commissioning via the Bluetooth interface of the circuit breaker
Notebook / PC via Bluetooth interface
To commission a communication module via the Bluetooth interface of the 3WA circuit
breaker, proceed as follows:
1. Connect your notebook/PC to the Bluetooth interface of the 3WA circuit breaker.
2. Start the SENTRON powerconfig configuration software.
3. In the SENTRON powerconfig configuration software, drag a 3WA circuit breaker into
the project.
4. Select the Bluetooth interface as gateway.
5. Load the current parameters of the 3WA circuit breaker into the project.
6. Edit the network parameters of the communication module.
7. Load the changed parameters into the 3WA circuit breaker.
The communication module can then be accessed under the set network parameters.