Accessories
4.3 Control and signaling accessories
3WA1 air circuit breaker
Equipment Manual, 02/2023, 92310000002-06
247
Up to five IOM230 digital input/output modules and up to five IOM350 input/output
modules can be connected to the CubicleBUS
2
. The CubicleBUS
2
address is assigned to
the module using the rotary coding switch. Each module must be given a unique number
between 1 and 5.
Note
Assignment of unique module numbers per module type
to 5 must be assigned to each of the IOM230 and IOM350
An IOM230 and an IOM350 can have the same number, but no number must ever be
assigned twice to one module type
.
For the selection of input/output modules, the most significant differences are described
in the following table.
Maximum continuous current of an output at 110 ... 230 V AC
Mounting on circuit breaker possible
Mounting on DIN rail possible
Maximum number of modules
Parameterization
The inputs and outputs can be configured using the SENTRON powerconfig
configuration software. For information on the SENTRON powerconfig configuration
software, refer to the internet (https://sie.ag/2SUlAc2
).
The following actions can be assigned to an input:
• Activate maintenance mode DAS+.
• Switch over to parameter set B.
• Set an input as "Input active".