Accessories
4.3 Control and signaling accessories
3WA1 air circuit breaker
Equipment Manual, 02/2023, 92310000002-06
249
IOM230 digital input/output module
(1)
CubicleBUS
2
connection
(6)
LEDs IN0 and IN1
(2)
Power supply connection
(7)
Setting switch for module number 1 - 5
(3)
Outputs
(8)
CUB LED (CubicleBUS
2
)
(4)
Inputs
(9)
ACT LED (Active)
(5)
LEDs OUT0 to OUT2
The IOM230 digital input/output module can be mounted on a DIN rail or on the
secondary disconnect terminal system of the air circuit breaker.
The IOM230 module features:
Two digital inputs
Three digital outputs
Active outputs are indicated by LEDs OUT0 to OUT2 and active inputs by IN0 and IN1.
The ACT (Active) LED indicates whether the module is ready and the CUB (CubicleBUS
2
)
LED indicates whether communication is taking place via the CubicleBUS
2
.
LED
Meaning
Description
ACT
On
Normal operation
Off
Module without power supply
Flashing
Restricted operating mode
CUB
On
CubicleBUS
2
communication normal
Off
No active CubicleBUS
2
nodes
ACT + CUB
Flashing
Identification is active