Technical specifications
6.5 Installation altitudes
3WA1 air circuit breaker
508 Equipment Manual, 02/2023, 92310000002-06
As
6)
and with the highest requirements regarding contact stability Class 3S1
Maximum drop height: 0.3 m
The device remains operational. Undisturbed operation under load is not guaranteed
in ev
ery case.
6.5 Installation altitudes
The low air density at installation altitudes above 2000 m can reduce heat dissipation.
This results in increased temperatures on the switching devices. The arcing behavior and
the conductivity of the density-dependent ionized gas mixture are also less favorable at
greater altitudes.
The following are reduced as a result:
• Operational voltage
• Operational current
• Short-time current
• Short-circuit breaking capacity
Maximum values of circuit breaker depending on installation altitude
Installation altitude up to
capacity
cu
6.6 Standards
The 3WA circuit breaker complies with the following standards:
• IEC 60947-2 / EN 60947-2 (emission limits according to CISPR 11 (Group 1/Class B)
and CISPR 32 (Class B))
• IEC 60692-2-5 / EN 60692-2-5
• ETSI EN 301 489-17 (only circuit breakers with radio function)
• ETSI EN 301 328 (only circuit breakers with radio function)
• EN IEC 63000