EasyManua.ls Logo

Siemens SENTRON 3WA1 - Page 515

Siemens SENTRON 3WA1
576 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical specifications
6.8 Failure probability acc. to B10 and B10d
3WA1 air circuit breaker
Equipment Manual, 02/2023, 92310000002-06
513
Premises
The determination of B10/B10d values acc. to IEC 62061 and ISO 13849-1 is based on
the following premises:
The devices comply with product standard IEC 60947-2. They are used according to
this standard and operate under undisturbed operating conditions.
Undisturbed operation can be guaranteed under rated conditions provided the
inspection intervals are observed:
At least 1 x per year
After each short-circuit trip
After five overload trips
After 1000 rated current trips ≤ 1000 V
After 500 rated current trips at 1150 V
Additional check of downstream non-automatic circuit breakers
As stipulated in ISO 13849-2, D.3, Table D.2, table row "Overdimensioning" and
IEC 62061, 6.7.9.2.2, Notes 1 and 2, the devices are subjected to underload such that
the current conducted through the switching contacts is less than half the rated
current I
n
.
It is assumed that the circuit breakers will only be integrated in a safety function via
an undervoltage release (closed-circuit principle).
B10 corresponds to the electrical endurance.
The percentage of dangerous failures is 50% acc. to ISO 13849-1, Table C.1, Note 1.
The B10d value is therefore calculated as: B10 / 0.5 = 2 x B10.
A lifetime (= T1 value) of 20 years is assumed.
According to ISO 13849-1, 3.1.28, 4.5.4 and C.4.2, the lifetime is the period which covers
the specified use of the device and during which the failure rate is regarded as constant.

Table of Contents

Related product manuals