Description
2.4 ETU300 electronic trip unit
3WA1 air circuit breaker
80 Equipment Manual, 02/2023, 92310000002-06
Two-stage overload alarm
Current is less than 90% of the set value Ir of
the overload protection
Current in a phase is between 90% and 100%
of the set value Ir of the overload protection
Current in a phase is greater than or equal to
the setting Ir of the overload protection
Display of status
information
DAS+ maintenance
mode
Last trip cause
If the ETU300 is not activated, the trip cause can be displayed by pressing the Query button. A
prerequisite for the display of the trip cause is that the ETU300 was activated for at least 2 hours
before the tripping operation. The trip cause is stored for 24 hours in this case.
Additional information on the display of error messages can be found in Chapter Display
of errors and alarms (Page 181).