Appendix
A.1 Modbus TCP
PAC2200
112 Equipment Manual, 12/2019, L1V30415167B-03
Table A- 8 Settings parameter for the digital input
Offset
Number of
registers
Name
Unit
Format
Value range
Access
50025 2 Digital input "Action" - unsigned long
0 =
Status only
RW
1 =
Pulse input
2 = High tariff / low
tariff switching
3 =
Synchronization
50029 2 "Pulse input" mode kWh unsigned long
0 =
0 kWh
RW
1 =
Export kWh
50031 2 Pulses per unit (pulses
per 1000 Wh / VARh)
- unsigned long 1 ... 4000 RW
50239 2 Input pulse divider kWh unsigned long
0 =
1 kWh
RW
1 =
10 kWh
2 =
100 kWh
3 =
1000 kWh
Table A- 9 Settings parameter for the digital output
Offset
Number of
registers
Name
Unit
Format
Value range
Access
50033 2 Switching function as-
signment to a vector
group
- unsigned long 0 ... 99 RW
50035 2 Digital output "Action" - unsigned long
0 =
Off
RW
1 =
Device ON
2 =
Switching output
3 =
Phase sequence
5 =
Energy pulse
50041 2 "Energy pulse" mode - unsigned long
0 =
Import kWh
RW
1 =
Export kWh
2 =
Import kVARh
3 =
Export kVARh
50043 2 Pulses per unit (pulses
per 1000 Wh / VARh)
- unsigned long 1 ... 4000 RW
50045
2
Pulse length
ms
unsigned long
30 ... 500
RW
50147 2 Digital output timeout s unsigned long 0 = AUS
0.1 ... 18000 = Output is
reset after expiry of the
time, provided there is no
operator input.
RW
50237 2 Output pulse divider kWh unsigned long
0 =
1 kWh
RW
1 =
10 kWh
2 =
100 kWh
3 =
1000 kWh