2.3 Averaging measured values
PAC2200
22 Equipment Manual, 12/2019, L1V30415167B-03
The following can be calculated from this: The last measuring period ended at 13:00. The
active measuring period will end at 13:15 or in 12 minutes.
Note
The power demand of the last measuring period can only be fetched during the current
measuring period.
Adjustable parameters
Period length in minutes: 1 to 60 min adjustable, default 15 min
2.3.2 Energy counters
Available energy counters of the PAC2200 measuring device:
Tariff 1
Tariff 2
Total
(T1 + T2)
Active energy kWh
Import
Total
X
X
X
L1
X
X
L2
X
X
L3
X
X
Secondary value
X (MID)
Export
Total
X
X
X
L1
X
X
L2
X
X
L3
X
X
Secondary value
X
Reactive energy kvarh
Import
Total
X
X
X
L1
X
X
L2
X
X
L3 X X
Secondary value
X
Export
Total
X
X
X
L1
X
X
L2
X
X
L3
X
X
Secondary value
X
Apparent energy kVAh
Total
X
X
X
L1
X
X
L2
X
X
L3
X
X
Secondary value
X