Description
2.5 Communication
PAC2200
36 Equipment Manual, 12/2019, L1V30415167B-03
As an example, the coding of the data record with ID 11 (connection type 1P2W, Mapping 1,
i.e. version 33) is more accurately explained in the RSP_UD2 response datagram:
Measured variable ID 11: Total reactive energy export tariff 2
DIF value format INT48 -> Integer 6 bytes length
VIF linear VIF extension -> actual VIF in first VIFE
Byte 4 0x82 VIFE reactive energy / unit kvarh
Integer value of measured variable
Version 33
Mapping 1
DIF/DIFE (default)
Version 33
Mapping 1
VIF/VIFE (default)
1 Secondary total active energy
1 0x86 0x10 0x03
Total active energy import tariff 1
Total active energy import tariff 2
Total active energy export tariff 1
Total active energy export tariff 2
L1 active energy import tariff 1
L1 active energy import tariff 2
L1 active energy export tariff 1
L1 active energy export tariff 2
L2 active energy import tariff 1
L2 active energy import tariff 2
L2 active energy export tariff 1
L2 active energy export tariff 2
L3 active energy import tariff 1
L3 active energy import tariff 2
L3 active energy export tariff 1
17 L3 active energy export tariff 2 1 0x86 0x20 0xFB 0x04
19 Active power L1 1 0x04 0x6D
DIF / VIF coding for version 33 (1P2W, Mapping 1)