Technical specifications
8.1 Technical specifications
PAC2200
90 Equipment Manual, 12/2019, L1V30415167B-03
Dimensions and weights
Dimensions and weights
Type of fixing
Standard rail mounting TH35 to EN 60715
Construction type
6TE
Housing dimensions W x H x D 108 mm x 97 mm x 71 mm
[4.2 in x 3.8 in x 2.8 in]
Weight
5 A device without packaging
310 g
5 A device with packaging
375 g
65 A device without packaging
415 g
65 A device with packaging
480 g
Degree of protection and protection class
Degree of protection and protection class
Protection class
Safety class II
Degree of protection according to IEC 60529
Front area
IP40
Termination area
IP20
If higher degree of protection requirements are placed on the application engineering, the
customer must take suitable measures. This includes installation in a protective enclosure
with degree of protection IP51 and higher
Environmental conditions
Operation is only permissible in a control cabinet or fuse box inside an enclosed dry room.
Environmental conditions
Temperature range
Ambient temperature during operating phase -25 °C … +55 °C
(K55)
Ambient temperature during transport and storage
-25 °C … +70 °C
Relative humidity (annual average value)
< 75 % RH
Installation altitude above sea level
max. 2000 m
Degree of pollution
2
Environmental tests according to
EN 60068-2-27
EN 60068-2-6
EN 60068-3-3

Table of Contents