EasyManua.ls Logo

Siemens SENTRON 7KT PAC1600 - Wiring Test

Siemens SENTRON 7KT PAC1600
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connection
5.3 Connecting three-phase device
7KT16 energy meter
Equipment Manual, 09/2020, 2514284147-04
75
Tightening torque Cable cross-section
(mm
2
)
L1 / N 63A
1.8 … 2.2
[15.9 ... 19.5]
2.5 … 16
RS 485 / S0 / M-Bus
0.14 … 0.16
[1.2 ... 1.4]
0.5 … 4
Parameterization
You can find information on parameterization in chapter Keypad functions (Page 19).
5.3 Connecting three-phase device
NOTICE
Irreparable device damage
The wrong system connection can cause irreparable damage to the device.
Before connecting the PAC1600, ensure that the local power supply conditions match the
specifications on the type plate.
Note
RS 485 termination is recommended!
In order to avoid reflection on the bus cable, we recommend fitting a 120
Ohm terminating
resistor at the beginning and end of the bus cable.
To
establish MODBUS RTU communication, the communication parameters must be known.
These include baud rate and format. Furthermore, you must enter the slave address in the
device.

Table of Contents

Related product manuals