MODBUS communication
11.6 Data library
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
159
11.6.2
Status bits (use with MODBUS function 03 and 04)
Address
Words
Function
Format
2070h 1
Status of keys of the user interface
Unsigned integer
2100h 1
Status of digital inputs (per PIN)
Unsigned integer
2140h 1
Status of digital outputs (per PIN)
Unsigned integer
-
-
-
-
2074h 1
Status of voltage Line 1
Unsigned integer
2075h 1
Status of breaker Line 1
Unsigned integer
2176h 1
Status of voltage, Line 2
Unsigned integer
2177h 1
Status of breaker Line 2
Unsigned integer
2078h 2
Status of function inputs
Unsigned integer
207Ah 1
Status of function outputs
Unsigned integer
207Bh 1
Status of message on display
Unsigned integer
207Ch 1
General status ATC
Unsigned integer
207Eh
1
Status of front LEDs
Unsigned integer
207Fh
1
Status of front LEDs
Unsigned integer
The 16 bits of the status Keys of the User Interface for the address 2070h have the
following meaning:
Bit
Key
0
1
OFF/ RESET
2
MAN
3
4
AUT / ✓
5…15
Not used