Technical data
PAC1020
70 Equipment Manual, 05/2020, L1V30610008B-01
Connection components: Digital inputs/outputs, RS485 interface
Connection components: Digital inputs/outputs, RS485 interface
Conductor cross-section for copper
cable (Cu)
Rigid
1 x 0.34 … 2.5 mm
2
(AWG 22 … 14)
Flexible
1 x 0.34 … 2.5 mm
2
(AWG 22 … 14)
Flexible with end sleeve, without plastic
sleeve
1x 0.34 … 1.0 mm
2
(AWG 22 … 18)
Flexible with end sleeve and plastic
sleeve
1x 0.34 … 1.0 mm
2
(AWG 22 … 18)
2 conductors with the same cross-
section
Rigid
2x 0.34 ... 0.5 mm
2
(AWG 22 … 20)
Flexible
2x 0.34 ... 0.5 mm
2
(AWG 22 … 20)
Flexible with end sleeve, without plastic
sleeve
1x 0.34 ... 0.5 mm²
(AWG 22...18)
Flexible with TWIN end sleeve and plas-
tic sleeve
1x 0.34 ... 1.0 mm²
(AWG 22...20)
Tightening torque
0.3 Nm
(2.6 lb-in)
Dimensions and weights
Dimensions and weights
Type of mounting
Panel mounting to IEC 61554
Enclosure dimensions W x H x D
96 mm x 96 mm x 46 mm
Cutout (W x H)
92 mm +0.8 mm x 92 mm +0.8 mm
Permissible panel thickness for installation
d = 1 ... 2 mm
In the case of panel thicknesses where
d ≠ 1 … 2 mm, installation is possible
using optionally available mounting
brackets (7KM9900-06A00-0AA0).