Appendix
A.1 Modbus
PAC1020
Equipment Manual, 05/2020, L1V30610008B-01
85
Offset Number of
registers
Name Format Unit Value range from ... to Access
to value (software)
read only / read
write
50011
2
Primary current
unsigned long
1 … 99999A
RW
50013
2
Secondary current
unsigned long
1, 5
RW
50019
2
Current direction
L1,L2,L3
unsigned long
0 … 7 bit-coded
Bit = 0 means normal,
Bit = 1 is inverse
.0 L1
.1 L2
.2 L3
RW
50025
2
Energy counter func-
tion
unsigned long
0 … 2 WORD-CODED
0 = import
1 = export
2 = net
HIWORD kVARh setting
LOWORD kWh setting
RW
50035
2
Digital output 0.0 ac-
tion
unsigned long
0 … 2
0 = no action
1 = switching output
2 = pulse output
RW
50037
2
Output 0.0 pulse type
index
unsigned long
0 … 3
0 = import kWh
1 = export kWh
2 = import kvarh
3 = export kvarh
RW
50039
2
Output 0.0 pulse ratio
(pulses per kWh/kvarh)
unsigned long
1-4000
RW
50041
2
Output 0.0 pulse
length
unsigned long
30-500
RW
50043
2
Digital output 0.0
Timeout
unsigned long
0.1 … 18000
Digital output remote
timeout = 118000
seconds
0 = disables timeout
(default)
RW
50045
2
Output 0.0 pulse divid-
er
unsigned long
0 … 3
0 = 1kWh
1 = 10kWh
2 = 100kWh
3 = 1000kWh
RW