Appendix
A.1 Modbus TCP
PAC2200
102 Manual, 05/2018, L1V30415167B-02
Applicable
Modbus func-
tion codes
63139 2 MODBUS RTU data
bits/ parity/ stop bits
(if RS485 port is
available)
- unsigned long
• 0x03
• 0x04
• 0x10
0 = 8N2
1 = 8E1
2 = 8O1
RW
63141 2 MODBUS RTU
response time (if
RS485 port is avail-
able)
ms unsigned long
• 0x03
• 0x04
• 0x10
1 - 255 RW
64001 27 IM0 data - IM0STRUCT
• 0x03
• 0x04
- R
64028 89 IM1 – IM4 data - IM14STRUCT
• 0x03
• 0x04
• 0x10
- RW
65290 2 Hardware write
protection ON/OFF
(requires pressing of
- unsigned long
• 0x10
RW
1 = OFF
Modbus device information with the function codes 0x03, 0x04 and 0x10
Addressing the device information parameters
You access the following device information parameters block-by-block only, e.g. read from
Offset 64001 27 Register.
Note
Error in the case of inconsistent access to I&M data.
Please ensure the start offset and the number of registers are correct when making read
accesses
and
. Always read or write the entire block.
Please ensure the start offset and the number of registers are correct when making write
accesses
.
If a value consists of several registers, a read command applied in the second register, for
example, will generate an error code. The PAC2200 will also output an error code if, for
example, a write operation ends in the middle of a multi
-register value.