Appendix
A.1 Modbus TCP
PAC2200
Manual, 05/2018, L1V30415167B-02
105
Offset
Number
of regis-
ters
Name
Unit
Format
Value range
Access
60009 1 Switching command for vector
group
- unsigned short High 0 ... 99, Low 0 ... 1
High byte group assign-
ment
Low byte 1 = ON,
0 = OFF
W
65300 1 Activation of IP / Ethernet
configuration
- unsigned short 0 W
3) The Modbus Master must acknowledge these diagnostics bits.
A.1.12
Modbus standard device identification with the function code 0x2B
Addressing the Modbus standard device identification
You can use Modbus function code 0x2B on these device identification parameters.
Table A- 14 Parameter for Modbus standard device identification
Object ID
Name
Format
Access
OID 0
Manufacturer
String
R
OID 1
Manufacturer device name
String
R
OID 2
Firmware version / bootloader version
String
R