Description
2.5 Communication
PAC2200
34 Manual, 05/2018, L1V30415167B-02
2.5.3.2
Single-phase connection (1P2W)
The measurement data is presented on one page.
All measurement data that can be read out via the M-BUS are listed in the following table.
ID
Measured variable
Length
(bits)
Format
Unit
1
Total active energy import tariff 1
48
INT48
Wh
2
Total active energy import tariff 2
48
INT48
Wh
3
Total active energy export tariff 1
48
INT48
Wh
4 Total active energy export tariff 2 48 INT48 Wh
5
Active power L1
32
FLOAT32
W
6
Voltage L1-N
32
FLOAT32
V
7
Current L1
32
FLOAT32
A
8
Total reactive energy import tariff 1
48
INT48
kvarh
9
Total reactive energy import tariff 2
48
INT48
kvarh
10
Total reactive energy export tariff 1
48
INT48
kvarh
11
Total reactive energy export tariff 2
48
INT48
kvarh
12
Reactive power L1 (VAR1)
32
FLOAT32
kvar
13
Power factor L1
32
FLOAT32
14
Frequency
32
FLOAT32
Hz
15
Tariff
8
INT8
16
Total apparent energy tariff 1
48
INT48
kVAh
17
Total apparent energy tariff 2
48
INT48
kVAh
18
Apparent power L1
32
FLOAT32
kVA
19
Date/time
32
time
As an example, the coding of the data record with ID 11 (connection type 1P2W, Mapping 1,