2.5 Communication
PAC2200
Manual, 05/2018, L1V30415167B-02
35
Measured variable ID 11:
Total reactive energy export tariff 2
BYTE No.
Coding
Description
Byte 1 0x86 DIF value format INT48 -> Inte-
ger 6 bytes length
Byte 2 0x20 DIFE tariff 2
Byte 3 0xFB VIF linear VIF extension ->
actual VIF in first VIFE
Byte 4 0x82 VIFE reactive energy / unit
kvarh
Bytes 5-6
0x3C
VIFE export
Bytes 7-12 XX XX XX XX XX XX Integer value of measured vari-
able
ID
Measured variable
Page
Version 33
Mapping 1
DIF /DIFE (de-
fault)
Version 33
Mapping 1
VIF/VIFE (default)
1 Secondary total active energy
(MID register)
1 0x86 0x10 0x03
2
Total active energy import tariff 1
1
0x86 0x20
0x03
3
Total active energy import tariff 2
1
0x86 0x10
0x83 0x3C
4
Total active energy export tariff 1
1
0x86 0x20
0x83 0x3C
5
Total active energy export tariff 2
1
0x05
0x2B
6
L1 active energy import tariff 1
1
0x05
0xFD 0x49
7
L1 active energy import tariff 2
1
0x05
0xFD 0x5C
8
L1 active energy export tariff 1
1
0x86 0x10
0xFB 0x02
9
L1 active energy export tariff 2
1
0x86 0x20
0xFB 0x02
10
L2 active energy import tariff 1
1
0x86 0x10
0xFB 0x82 0x3C
11 L2 active energy import tariff 2 1 0x86 0x20 0xFB 0x82 0x3C
12
L2 active energy export tariff 1
1
0x05
0xFB 0x17
13 L2 active energy export tariff 2 1 0x05 0xFD 0x67
14
L3 active energy import tariff 1
1
0x05
0xFB 0x2F
15
L3 active energy import tariff 2
1
0x01
0xFD 0x67
16
L3 active energy export tariff 1
1
0x86 0x10
0xFB 0x04
17
L3 active energy export tariff 2
1
0x86 0x20
0xFB 0x04
18
Total active power
1
0x05
0xFB 0x57
19
Active power L1
1
0x04
0x6D
DIF / VIF coding for version 33 (1P2W, Mapping 1)