Description
2.5 Communication
PAC2200
36 Manual, 05/2018, L1V30415167B-02
ID
Measured variable
Page
Version 31
Mapping 0
DIF / DIFE
Version 31
Mapping 0
VIF / VIFE
1 Secondary total active energy
(MID register)
1 0x86 0x10 0x03
2 Total active energy import tariff 1 1 0x86 0x20 0x03
3
Total active energy import tariff 2
1
0x86 0x10
0x03
4
Total active energy export tariff 1
1
0x86 0x20
0x03
5
Total active energy export tariff 2
1
0x05
0x2B
6
L1 active energy import tariff 1
1
0x05
0xFD 0x49
7
L1 active energy import tariff 2
1
0x05
0xFD 0x5C
8
L1 active energy export tariff 1
1
0x86 0x10
0xFB 0x02
9
L1 active energy export tariff 2
1
0x86 0x20
0xFB 0x02
10
L2 active energy import tariff 1
1
0x86 0x10
0xFB 0x02
11
L2 active energy import tariff 2
1
0x86 0x20
0xFB 0x02
12
L2 active energy export tariff 1
1
0x05
0xFB 0x17
13
L2 active energy export tariff 2
1
0x05
0xFD 0x67
14
L3 active energy import tariff 1
1
0x05
0xFB 0x2F
15
L3 active energy import tariff 2
1
0x01
0xFD 0x67
16
L3 active energy export tariff 1
1
0x86 0x10
0xFB 0x04
17
L3 active energy export tariff 2
1
0x86 0x20
0xFB 0x04
18
Total active power
1
0x05
0xFB 0x37
19
Active power L1
1
0x04
0x6D
DIF / VIF coding for version 31 (1P2W, Mapping 0)