Connection
4.4 Connecting the communication cable
PAC2200
Manual, 05/2018, L1V30415167B-02
45
Connection example for 65A device
(1) Three-phase measurement, four conductors, direct connection to the low-voltage network
*
The fuses in the voltage measuring inputs are only used for cable protection.
Figure 4-5 Direct connection to the low-voltage network.
4.4
Connecting the communication cable
Depending on the device version, the following communication interfaces are available:
● Ethernet
RS 485
● M-BUS
4.4.1
Ethernet communication cable
This interface is available as an option.
Always use a shielded cable for the Ethernet data cable.
1. Plug the RJ 45 cable connector into the RJ 45 device socket until the connector engages
in the socket.
2. Provide sufficient mechanical strain relief for the Ethernet cable.
3. Ground the shield of the cable (see chapter 4.4.4 Grounding of the Ethernet / RS 485
cable).