Commissioning
6.3 Parameterizing the device
PAC2200
Manual, 05/2018, L1V30415167B-02
69
"Extended" parameter
"Password" parameter
The write access to the device settings can be protected by means of a password.
As soon as the password has been entered once for the device, it is not requested again for
as long as the device is still in the "Settings" menu.
Display
No: Password protection deactivated
Yes: Write access is password protected using keys on display
(default setting: No)
Communication
No: Password protection deactivated
Yes: Write access is password protected by means of communication
(default setting: No)
Password
Password policy four-digit number between 0000 ... 9999
(default setting 0000)
Note
If you have
forgotten the password, please contact Technical Support. You will receive a
new password from them.
"Reset" parameter
Factory settings
All device settings and measured values except the communic
a-
tion parameters and energy secondary values are reset
to the as-
delivered condition.
No: Not active
Yes: active
Communication settings
All communication settings are reset to the as-delivered condition.
No: Not active
Yes: active
Execute
Confirmation of the reset
Note
The reset must be confirmed by selecting the "Execute..." field. Otherwise the device reset is
not executed.