Appendix
A.1 Modbus
PAC3120 and PAC3220
Equipment Manual, 10/2019, L1V30425208F-01
127
Offset
Number of
registers
Name
Unit
Format
Value range
Access
50145 2 Limit 5 Type /< Unsigned
long
0 … 1
0 = Greater than
1 = Smaller than
RW
50147 2 DO 0.0 Timeout Unsigned
long
0.1 18000
Digital output remote timeout
1 18000 s, 0 = Disables
timeout (default)
RW
50149 2 Default menu No. Unsigned
long
DISPLAYED MENU
NUMBER:
1 29: Only existing menus
are accepted
1 = MEAS_VLN
2 = MEAS_VLL
3 = MEAS_I
4 = MEAS_S
5 = MEAS_P
6 = MEAS_Q
7 = MEAS_SPQ
8 = MEAS_PF
9 = MEAS_COS
10 = MEAS_F
11 = EAS_IMBALM
12 = MEAS_THDI
13 = MEAS_THDU
14 = MEAS_THDULL
15 = MEAS_WORK_S
16 = MEAS_WORK_P
17 = MEAS_WORK_Q
18 = MEAS_COUNTER
19 = MEAS_WORKHOUR
20 = MEAS_MODUL1 (valid
only if measuring module
(e.g. I-N module) plugged in
slot "Mod1")
21 = MEAS_MODUL2 (valid
only if measuring module
(e.g. I-N module) plugged in
slot "Mod2")
RW
50151 2 Timeout for return to default menu Unsigned
long
0 3600 s
0 = No timeout
10 3600 s
1 s timeout < 10 s: timeout
is set to 10 s
RW
50231 2 Date format Unsigned
long
0 … 2
0 = dd.mm.yyyy
1 = mm/dd/yy
2 = yyyy-mm-dd
RW
50233 2 Daylight saving Unsigned
long
0 … 3
0 = No
1 = Auto EU
2 = Auto US
3 = Daylight saving table
RW