Appendix
A.1 Modbus
128
PAC3120 and PAC3220
Equipment Manual, 10/2019, L1V30425208F-01
50237 2 DO 0.0 Pulse divider – Unsigned
long
0 … 3
0 = 1 kWh
1 = 10 kWh
2 = 100 kWh
RW
50239 2 DI 0.0 Pulse divider – Unsigned
long
0 … 3
0 = 1 kWh
1 = 10 kWh
2 = 100 kWh
RW
50243 2 Current direction L1 yes/no – Unsigned
long
0 … 1
0 = No
RW
50245 2 Current direction L2 yes/no – Unsigned
long
0 … 1
0 = No
RW
50247 2 Current direction L3 yes/no – Unsigned
long
0 … 1
0 = No
RW
51199 1 DI 0.0 Type of use – Unsigned
short
0 … 3
0 = No action
1 = Pulse interface
2 = Switching on/off peak
3 = Synchronization
RW
51201 1 DI 0.0 Index – Unsigned
short
0 … 1
0 = kWh
RW
51202 1 DI 0.0 Pulses per kWh/kvarh – Unsigned
1 … 4000 RW
51203 1 DI 0.0 Pulse divider – Unsigned
– RW
51204 1 DI 0.1 Type of use – Unsigned
short
0 … 3
0 = No action
1 = Pulse interface
2 = Switching on/off peak
RW
51206 1 DI 0.1 Index – Unsigned
short
0 … 1
0 = kWh
RW
51207 1 DI 0.1 Pulses per kWh/kvarh – Unsigned
1 … 4000 RW
51208 1 DI 0.1 Pulse divider – Unsigned
short
– RW
51209 1 DI 4.0 Type of use – Unsigned
short
0 … 3
0 = No action
1 = Pulse interface
2 = Switching on/off peak
RW