Parameterize
9.2 Parameterizing the operator interface
SENTRON PAC3200
Manual, 02/2008, A5E01168664B-04
145
PICKUP DELAY Delay in reporting limit violation in seconds.
The delay refers to the occurrence of the limit
violation or the point of exceeding the threshold
defined in the "VALUE" field. See the figure below
"Effect of delay".
Range: 0 to 10 s
Default: 0 s
HYSTERESIS Threshold buffer, prolongs the limit violation.
The hysteresis refers to the disappearance of the limit
violation or the point when the level returns below the
defined threshold.
Range: 0.0 to 20.0%
Default: 0,0 %
The percentage value refers to the threshold value in
the VALUE field. See the figure below "Effect of
delay"